IEC60092 Offshore & Marine Cables | |||
MariTox Marine Flame Retardant Medium Voltage Cables | MariTox Marine Flame Retardant Power & Control Cables | MariFlex Marine Fire Resistant Power & Control Cables | other |
Power Distribution Cables
5000V single conductors Type E, X distribution cables
Construction
Conductor: Stranded copper conductor tin or alloy coated where necessary for the application , conductor per
ASTM or IEC 60228.
Separator tape: optional
Insulation: Ethylene propylene rubber(EPR), or cross-linked polyethylene(XLPE) according to IEEE 1580 2010
Type E, X,Type T, T/N, S, P, LSX and LSE as option.
Shielding: optional
Jacket: Thermosetting Polychloroprene(neoprene) according to IEEE 1580 2010 Type N, Type T, CP, CPE, L, P or
TPO jacket as option (optional for Type P with HD thicknesses).
Armor: optional and shall be nonmagnetic
Sheath: Thermosetting Polychloroprene(neoprene) according to IEEE 1580 2010 Type N, Type T, CP, CPE, L, P
or TPO sheath as option (optional except for tinned copper braid armoured cables).
Optional: For halogen-free constructions, Type LSX, LSE or LSS insulation shall be used with a Type L or TPO
jacket/sheath.
Table B.7—Typical Dimensions and weights; one conductor 5000 V; Type E and X distribution cables
AWG /kcmil |
Unarmored | Armored | Armored and sheathed | |||
---|---|---|---|---|---|---|
Nom. dia. (in) | Approx. weight (lb/1000 ft) | Nom. dia. (in) | Approx. weight (lb/1000 ft) | Nom. dia. (in) | Approx. weight (lb/1000 ft) | |
8 | 0.58 | 234 | 0.64 | 265 | 0.76 | 346 |
6 | 0.61 | 279 | 0.67 | 312 | 0.79 | 396 |
4 | 0.66 | 345 | 0.72 | 380 | 0.89 | 512 |
2 | 0.72 | 453 | 0.78 | 490 | 0.95 | 632 |
1 | 0.77 | 525 | 0.83 | 565 | 1 | 715 |
1/0 | 0.8 | 608 | 0.86 | 648 | 1.03 | 802 |
2/0 | 0.89 | 755 | 0.95 | 800 | 1.12 | 970 |
3/0 | 0.94 | 883 | 1 | 930 | 1.17 | 1107 |
4/0 | 1 | 1050 | 1.06 | 1100 | 1.23 | 1288 |
250 kcmil | 1.04 | 1192 | 1.1 | 1245 | 1.27 | 1439 |
300 kcmil | 1.1 | 1376 | 1.16 | 1432 | 1.33 | 1636 |
350 kcmil | 1.15 | 1557 | 1.21 | 1616 | 1.38 | 1828 |
400 kcmil | 1.2 | 1740 | 1.26 | 1802 | 1.43 | 2023 |
500 kcmil | 1.3 | 2111 | 1.36 | 2179 | 1.53 | 2416 |
600 kcmil | 1.38 | 2462 | 1.44 | 2536 | 1.61 | 2786 |
750 kcmil | 1.49 | 2669 | 1.55 | 2747 | 1.78 | 3117 |
1000 kcmil | 1.64 | 3835 | 1.7 | 3921 | 1.93 | 4323 |
NOTE—These values are for reference purposes only and should not be construed as requirements. Dimensions are based on the use of Class B conductors. Weights of armored constructions are based onaluminum braid armor. It is recommended that the user/specifier contact the manufacturer for manufacturer specific values.